Transformer Ratings | Voltage Rating, Current Rating, Power Rating

To properly use a transformer, one must know its voltage and current ratings. Of course, from these ratings the power rating of the transformer can be calculated. Most transformers are also specified by their voltampere (apparent power) ratings.

Voltage Rating of Transformer

Manufacturers always specify the voltage rating of the primary and secondary windings. Operating the primary above rated voltage usually causes the transformer to overheat. The additional stress placed on the transformer insulation by the higher primary and secondary voltages can also be serious. Operating the primary below rated voltage does no harm, but this makes the secondary voltages lower than rated values.

The rated voltages of the secondaries are specified for full-load conditions with rated primary voltage. With no load, the secondary voltage is slightly higher than rated voltage (usually 5 to 10 percent higher).

There is considerable variation in the way in which manufacturers specify center-tapped secondaries. For example, the secondary in Figure 1 may be specified in any of the ­following ways:

  1. 40 V C.T.
  2. 20 V-0-20 V
  3. 20 V each side of center

Center-tapped Transformmer secondary specifications.

Figure 1. Center-tapped Transformmer secondary specifications. The secondary is classified as either 40 V center-tapped or 20 V each side of center.

Current Rating of Transformer

Manufacturers usually specify current ratings for secondary windings only. As long as the secondary current rating is not exceeded, the primary current-carrying capacity cannot be ­exceeded.

Exceeding the current rating of a secondary causes its voltage to fall slightly below rated value. More serious than decreased voltage, however, is the increase in I2R loss in the secondary. The increased I2R loss causes the winding to overheat and eventually destroys the transformer.

Power Rating of Transformer

Some manufacturers specify a power rating (in watts) for their transformers. This is understood to be the power the transformer can deliver to a resistive load. Thus, the power rating is merely the product of the current rating and the voltage rating of the secondary (P = VI). For multiple-secondary transformers, the power rating is the sum of the powers available from the individual secondaries (PT = P1 + P2 + etc.). The total power cannot be taken from a single secondary on a multiple-secondary transformer. The current rating of the individual secondaries must not be exceeded.

Voltampere (kVA) Rating of Transformer

The voltampere rating of a transformer is an apparent power rating. It is applicable to any type of load—resistive, reactive, or combination (impedance). The voltampere rating, like the power rating, is given for the total transformer instead of for individual secondaries. With a multiple-secondary transformer, the total voltampere rating cannot be taken from a ­single secondary.

A transformer can be loaded to its full voltampere rating and be delivering only a fraction of its power rating. Refer to Figure 2 for an example. Here the load is a motor which has a power factor (cosθ) of 0.6. It is connected to a transformer that is rated at 750 VA and has a secondary voltage of 120 V. The motor draws 6.25 A. The transformer provides 750 VA (120 VA x 6.25 A). However, the motor is drawing only 450 W (P = VI cosθ = 120 x 6.25 A x 0.6).

Voltampere Rating of Transformer diagram

Figure 2. Voltampere versus power rating. The limiting rating is the voltampere rating.

As you can see, manufacturers use many ways to rate transformers. You will never overload a transformer or exceed any of its ratings if you observe two rules.

  • Never apply more than the rated voltage to the primary.

  • Never draw more than the rated current from any secondary.

Transformer Ratings FAQs

True or false. It is not possible to exceed the voltampere rating of a transformer without exceeding the power rating of the transformer.

True or false. The power rating of a transformer can be exceeded without exceeding either the primary voltage rating or the secondary current rating.

True or false. The voltampere rating of a transformer cannot be exceeded without exceeding either the primary voltage rating or the secondary current rating.

True or false. Secondary voltages are rated at full load current and rated ­primary voltage.

Answers:

  1. F
  2. F
  3. T
  4. T

Transformer Ratings Example

You need to operate a 240-V device that draws 10 A and has a PF of 0.8 from a 120-V source. Determine the minimum specification for a transformer needed to do the job.

Given.

Load Voltage = 240 V

Load Current = 10 A

Load Power Factor = 0.8

Source Voltage = 120 V

Find.

Transformer windings voltages Transformer power rating

Known.

VPri = VSource

VSec = VLoad

PApparent = VA

Solution.

VPri = VSource = 120 V

VSec = VLoad = 240 V

PApparent = VLoad x VLoad = 240 V x 10 A = 2400 VA = 2.4 kVA

Answer:

An iron-core transformer rated at 2.4 kVA (or higher) with a 120-V primary and a 240-V secondary.

The transformer in example 1 could also have a 120-V primary and a 240-V secondary rated at 10 A.